Performance Data Sheet
AJE4492YXA
General Information
Model AJE4492YXA Refrigerant R-134a
Test Condition EN12900 ASERCOM Performance Test Voltage 115V ~ 60HZ
Return Gas 20°C (68°F) RETURN GAS Motor Type CSIR
Performance Information
Condensing Temperature (°C)
Evap
Temp (°C)
30 40 50 60
Watts
(Capacity)
1940 1680 1300 832
Watts (Power) 746 814 819 725
-6.7
Amps 10.4 10.6 10.6 10.4
Watts
(Capacity)
2100 1830 1440 955
Watts (Power) 769 844 863 787
-5
Amps 10.6 10.9 10.9 10.8
Watts
(Capacity)
2610 2310 1880 1340
Watts (Power) 839 931 982 956
0
Amps 11.1 11.6 11.9 11.9
Watts
(Capacity)
3190 2850 2370 1770
Watts (Power) 919 1020 1090 1110
5
Amps 11.6 12.3 12.8 13.0
Watts
(Capacity)
3470 3110 2600 1970
Watts (Power) 960 1060 1140 1170
7.2
Amps 11.8 12.7 13.2 13.6
Watts
(Capacity)
3850 3460 2920 2240
Watts (Power) 1020 1120 1210 1250
10
Amps 12.2 13.1 13.8 14.2
Watts
(Capacity)
4610 4160 3540 2780
Watts (Power) 1140 1230 1320 1390
15
Amps 12.8 13.9 14.8 15.5
COEFFICIENTS CAPACITY POWER CURRENT MASS FLOW
C1 2.366506E+03 6.842346E+02 7.924028E+00
C2 1.158684E+02 2.707010E+01 -2.377131E-02
C3 4.273324E+01 -5.315154E+00 1.426768E-01
Komentarze do niniejszej Instrukcji